product type miniature circuit breaker number of poles 1P/2P/3P/4P Product Application Di……
product type miniature circuit breaker
number of poles 1P/2P/3P/4P
Product Application Distribution protection
Number of protection poles 1,2,3,4
Rated current (In) 100 A at… 30 ° C
Type of release device thermo-magnetic
Release curve C
Breaking Capacity 10 kA Icu on… 440 V AC 50/60 Hz in accordance with IEC 60947-2
30 kA Icu on… 230… 240 V AC 50/60 Hz in accordance with IEC 60947-2
15 kA Icu on… 400… 415 V AC 50/60 Hz in accordance with IEC 60947-2
15000 A Icn on… 400 V AC 50/60 Hz in accordance with IEC 60898-1
Isolation function Applicable in accordance with IEC 60947-2
main information
Network frequency 50/60 Hz
Rated working voltage [Ue] 230 V AC/400 V AC 50/60 Hz
Magnetic release limit 5…10 x In
Current limiting level 3. Complies with IEC 60898-1
Rated insulation voltage [Ui] 500 V AC 50/60 Hz in accordance with IEC 60947-2
Rated impulse withstand voltage [Uimp] 6 kV complies with IEC 60947-2
Contact position indication have
control type handle
Local signal indication On/off indication
Installation type Locking clip locking
Installation method DIN rail installation
mechanical life 20000 times
Electrical life 5000 times
Wiring ability Tunnel type terminal with upper or lower wiring 1… 50 mm ² single stranded hard wire without wire terminal
Tunnel terminal with or without wire connection, 1.5… 35 mm ² flexible wire (optional)